The common troubleshooting for Ice Qube Air Conditioner. symptom : Unit not cooling. Is the evaporator fan operating ?
If the evaporator fan is operating … What is the status of the Cool LED on the display ? If the Cool LED is flashing, within 3.5 minutes, the Cool LED should be lit continuous, and cooling should begin. When the Cool LED is lit continuous, the compressor and condenser blower should be operating. Controller display blank. This indicates loss of power to the controller or a defective controller.
Check the output voltage at the transformer secondary. The voltage should be a nominal 24 VAC. If the proper voltage is available at the transformer and the controller harness is secure to the controller, the controller is most likely faulty. Unit cooling, but cabinet temperature too high (High Temperature Alarm) Check the settings of the temperature controller. Decrease cool on temperature if required. Has equipment been recently been added to the enclosure ? Is the condenser air filter clean ? See operation manual for instructions. What is the temperature differential of the return air inlet and the cold air outlet “ This temperature differential should be a minimum of 10 deg. F within 15 to 30 minutes of compressor operation unless the air is very humid. Are doors on the enclosure closed ?

Tags : compressor operation, faulty unit, proper voltage, temperature alarm, temperature controller, condenser, ice qube, output voltage, air filter, air conditioner, air conditioners, high temperature, cold air, differential, 30 minutes
If you see unrelated pdf files with the description or copyrighted material published, please report to us, we'll correct/delete it it as soon as possible.NONE OF THOSE MATERIALS ARE HOSTED IN THIS SERVER NOR UPLOADED BY ME IN SOMEONE'S SERVERS.  Read our DISCLAIMER for more detail.
We are neither affiliated with authors and brands nor responsible for its content and change of content.
Information contained herein is provided "as is" without warranty of any kind, either expressed or implied, including any warranty of merchantability or fitness for a particular purpose. In no event shall ANYONE be held liable for any loss of profit, special, incidental, consequential, or other similar claims.